Chillers and air cooled heat pumps from the MultiPower series.
MultiPower units, which feature exceptional control capabilities and high reliability parameters, are dedicated to air conditioning and heating of buildings.
MultiPower units, which feature exceptional control capabilities and high reliability parameters, are dedicated to air conditioning and heating of buildings.
Units with the refrigeration system containing R410A (GWP 2088) refrigerant.
Scroll compressor with an oil sight glass. Installed with internal overheating protection and, if required, with a crankcase heater, fitted on rubber vibration dampers.
Axial fans directly coupled to a three phase electric motor and external rotor, equipped with a grille protecting the fan located at the air outlet.
Units in the cooling/heating version operate using the heat pump function. They can cool or heat water, chilled water or air.
The units in the cooling-only version provide the basic function of cooling water, chilled water or air, while other functions are optional.
Shell and tube heat exchanger with two independent cooling circuits and one water circuit.
Units with the refrigeration system containing R452B (GWP 675) refrigerant.
Agregat
|
EER* COP* |
Wydajność C/G |
Pobór mocy C/G |
Zasilanie |
Wymiary |
Masa Tylko chłodzenie/ Pompa ciepła |
Ładunek czynnika Tylko chłodzenie/ Pompa ciepła |
|
|
kW |
kW |
V/pH/Hz |
mm |
kg |
kg (CO2eq-T) |
CHA/K 726 |
2,80 3,03 |
200 229 |
70 74 |
400/3/50 |
2100/2800/2200 |
1703/ 1853 |
2x17(2x35496)/ 2x19(2x39,672) |
CHA/K 786 |
2,75 2,98 |
224 252 |
80 83 |
400/3/50 |
2100/2800/2200 |
1723/ 1873 |
2x17(2x35496)/ 2x19(2x39,672) |
CHA/K 826 |
2,84 2,99 |
248 280 |
86 91 |
400/3/50 |
2100/2800/2200 |
1813/ 1933 |
2x17(2x35496)/ 2x19(2x39,672) |
CHA/K 906 |
2,74 2,81 |
270 304 |
97 106 |
400/3/50 |
2100/2800/2200 |
2003/ 2133 |
2x23(2x48,024)/ 2x25(2x52,200) |
CHA/K 1048 |
2,84 3,02 |
302 336 |
105 109 |
400/3/50 |
2100/4000/2200 |
2253/ 2433 |
2x25(2x52,200)/ 2x27(2x56,376) |
CHA/K 1128 |
2,79 2,87 |
328 362 |
115 123 |
400/3/50 |
2100/4000/2200 |
2532/ 2712 |
2x30(2x62,640)/ 2x33(2x68,904) |
CHA/K 1208 |
2,97 3,01 |
367 401 |
121 130 |
400/3/50 |
2100/4000/2200 |
2642/ 2822 |
2x30(2x62,640)/ 2x33(2x68,904) |
CHA/K 13010 |
2,94 2,98 |
404 442 |
136 145 |
400/3/50 |
2100/4000/2200 |
2691/ 2881 |
2x33(2x68,904)/ 2x37(2x77,256) |
CHA/K 15010 |
2,79 3,01 |
445 512 |
158 167 |
400/3/50 |
2100/5000/2200 |
3283/ 3523 |
2x33(2x68,904)/ 2x37(2x77,256) |
CHA/K 16812 |
2,89 3,05 |
510 581 |
174 186 |
400/3/50 |
2100/5000/2200 |
3383/ 3633 |
2x42(2x87,696)/ 2x46(2x96,048) |
CHA/K 18012 |
2,92 2,98 |
551 626 |
186 204 |
400/3/50 |
2100/5000/2200 |
3565/ 3835 |
2x42(2x87,696)/ 2x46(2x96,048) |
CHA/K 21012 |
2,82 3,00 |
614 698 |
214 226 |
400/3/50 |
2100/5000/2200 |
3605/ 3875 |
2x43(2x89,784)/ 2x47(2x98,136) |
CHA/K 24012 |
2,71 3,00 |
684 791 |
250 257 |
400/3/50 |
2100/5000/2200 |
3840/ 4130 |
2x45(2x93,960)/ 2x49(2x102,312) |
CHA/K 27012 |
2,69 2,96 |
766 878 |
281 288 |
400/3/50 |
2100/6200/2200 |
4385/ 4675 |
2x55(2x114,840)/ 2x60(2x125,280) |
CHA/K 30012 |
2,76 3,01 |
862 981 |
307 316 |
400/3/50 |
2100/6200/2200 |
4705/ 4995 |
2x55(2x114,840)/ 2x60(2x125,280) |
CHA/K 33012 |
2,79 3,04 |
961 1100 |
340 353 |
400/3/50 |
2100/7200/2200 |
5210/ 5520 |
2x65(2x135,720)/ 2x70(2x146,160) |
CHA/K 36012 |
2,84 3,06 |
1062 1222 |
369 388 |
400/3/50 |
2100/7200/2200 |
5330/ 5640 |
2x66(2x137,808)/ 2x71(2x148,248) |
Dane techniczne dotyczą wybranych modeli z oferty Klima-Therm. Producent stale udoskonala swoje wyroby – aby zweryfikować dane proszę skontaktować się z Autoryzowanym Dealerem. C - chłodzenie, G – grzanie. Nominalna wydajność chłodzenia i grzania wyznaczana jest dla następujących parametrów: tryb chłodzenia temperatura wody chłodzonej 12°/7°C, temperatura powietrza zewnętrznego 35°C; tryb grzania temperatura wody grzewczej 40°/45°C, temperatura powietrza zewnętrznego 7°C,
*EN14511