Air conditioning configurator

close
Air conditioning configurator

The HOP line of precision air conditioners is the most advanced solution for technological applications in facilities such as: server farms, power amplifier rooms of UMTS and GSM transmitters, NOCs (Network Operations Centre), cooling of computer racks, control rooms, power supply devices, and practically anywhere where heat loads are extremely high.

 

The principle of operation: the room air is treated in an evaporator through which the refrigerant flows; the condensation heat is discharged to a built-in plate exchanger water/freon.

  • Innovative design
  • Compact units
  • EC type "Plug-Fan"
  • Scroll compressor
  • Simple maintenance
  • Low noise operation
WATERCOOLED DIRECT EXPANSION UNITS with EC Inverter Plug-Fans
  • Rated cooling capacity: 9,6 / 152 kW
  • Rated heating capacity: 3,5 / 31 kW
  • The capacity of the humidifier: 4 / 15 kg/h
  • Suitable for operation at outdoor temperatures up to 52?C
  • Self-supporting frame, internal elements of the housing made of galvanized steel sheet.
  • From the inside the casing has thermal and acoustic insulation with the fire resistance class A1.
  • Access to all components is possible from the front of the unit through hinged doors.
  • Three-phase hermetic Scroll type compressor equipped with brushless DC engine, inverter controlled.
  • In devices with two cooling circuits, in the event of a fault in one of the systems, operation of the unit with 50% cooling capacity is guaranteed.
  • 60% lower energy consumption by supply elements.
  • Higher efficiency even at partial load.
  • The fan speed can be adjusted and modified using the microprocessor, without interrupting the device
  • It is possible to adjust the air flow to the required pressure.
  • Filters in high class M5 filtration are made of latex and fibers with high filtering ability.
  • Constructions of heat exchangers guarantee a high level of heat exchange and low air pressure drops.
  • Differential pressure sensor for fan speed and filter contamination control.
  • AP, HT, DPS, AR, AT, AT/P, PF, EH, WS, UMI, SA, IS, IS/B, IS/BT, ISL, WM, MP, MP/U, FF, FM, CR, ZP, ZA, DL, BA, BM, DM, BV
Technical specifications

Model

 

EER

 

Wydajność

Chłodnicza

kW

Pobór mocy

kW

Zasilanie

V/Ph/Hz

Wymiary

HxWxD

Masa

kg

1009

4,30

9,6

2,2

 

230 / 1 / 50

1980x675x675

248

1013

4,56

13,1

2,9

1980x675x675

255

1017

4,66

17,2

3,7

 

 

 

 

 

 

 

 

 

 

400/3+N/50

1980x675x675

268

1019

4,27

18,8

4,4

1980x675x675

268

1023

4,35

23,1

5,3

1980x875x675

302

1029

4,54

28,8

6,4

1980x875x675

321

1037

4,25

37,3

8,8

1980x1350x890

458

1043

4,14

42,7

10,3

1980x1750x890

492

2051

4,31

50,8

11,8

1980x1350x890

532

2058

4,58

58,2

12,7

1980x1350x890

556

2072

4,50

71,6

15,9

1980x1350x890

668

1074

4,51

74,2

16,5

1980x1750x890

669

2088

4,66

88,1

18,9

1980x1750x890

801

2099

4,42

99,5

22,5

1980x2225x890

823

2110

4,25

110

25,9

1980x2225x890

853

2117

4,41

117

26,6

1980x2625x890

960

2152

4,60

152

33,0

1980x2625x890

1077

 

Temperatura otoczenia 24 °C - R.H. 50%; Temperatura skraplania 45 °C.

Temperatura wody 7°C / 12°C

Ciśnienie dźwięku mierzone w wolnej przestrzeni, w odległości 2 m od urządzenia (ISO 3744), z kanałami podłączonymi na wylocie i wlocie powietrza (z wyjątkiem wlotu w wersji z wlotem OD GÓRY).